Okay, this is a comprehensive set of data across your requirements and multiple vendors. I will compile a report comparing each vendor’s offering against your detailed “Table 1” specifications for each valve.

I’ve extracted the most relevant information for comparison from your Table 1 data and cross-referenced it with the details provided for Masoneilan, Samson (from previous turns), and the new Flowserve (CTi Controltech) quote.


Comprehensive Control Valve Vendor Comparison Report

Purpose: To evaluate and compare the technical offers from Masoneilan, Samson, and Flowserve (CTi Controltech) against the specified requirements for each control valve listed in “Table 1”.

Key Considerations for Decision:

  1. Technical Adherence to Specifications: How well does each vendor meet the specified valve type, size, material, fail position, trim, leakage, and performance (Cv, noise, travel) requirements?
  2. Completeness of Scope: Do all vendors quote for all required valves?
  3. Pricing: What is the total cost for the compliant packages?
  4. Lead Time: What are the quoted delivery times?
  5. Technical Justification for Deviations: Are any deviations from specifications clearly justified (e.g., larger size for noise reduction)?

Summary of Vendors’ Offerings

Vendor Overall Adherence to Specs Missing Valves (from Table 1) Common Deviations/Notes
Masoneilan Good, minor size opt. 131-PCV-0583, 131-PCV-0585C, 131-PV-0581 Offers larger actual valve sizes than specified for some items (e.g., 4" for 2" line). Good Cv match.
Samson Significant Size Mismatches 131-PCV-0583, 131-PCV-0585C, 131-PV-0581 Frequent and significant deviations in valve size vs. specified pipe size. Justified by noise reduction for some. Generic “Metallic” trim needs clarification.
Flowserve Good, with Rotary Options 131-PCV-0583, 131-PCV-0585C, 131-PV-0581 Offers both Globe and cheaper Rotary alternatives. Excellent detail on trim materials, leakage, and noise. Minor positioner model number discrepancy.

Detailed Valve-by-Valve Comparison

Legend:


1. Valve Tag: 131-TV-0348 (Lube Oil Cooler Bypass)

Feature Masoneilan Samson Flowserve (CTi Controltech)
Valve Model 88-41315 Globe Globe Valve Valtek Mark One Globe
Size/Pipe 6" / 6" Sch. XS (Match) DN 6" / 6" Sch. XS (Match) 6" / Pipe 6" Sch. XS (Match)
Connection 300# RF (Match) 300# RF (Match) 300# RF (Match)
Fail Pos. FC (Match) FC (Match) FC (Match)
Body Mat. A216 gr WCC (CS - Match) A216 WCC (CS - Match) WCC (CS - Match)
Trim Type Linear Contoured (Allowed) Equal Percentage (Allowed) Standard / Equal Percent (Allowed)
Trim Mat. 17-4PH St. St. / 410 St. St. (Match SS) Metallic (Clarify if SS) 316 SS (Match SS)
Rated Cv 400 (Req Cv 224.7) - Good margin 400 - Good margin 87.823 (matches Flowserve’s sizing calculation)
Noise < 70 dBA (Match ≤ 85) < 70 dBA (Match ≤ 85) < 70 dBA (Match ≤ 85)
Positioner Identical (HART/Smart) Identified in sizing report Logix 3800 Series / 3821 (HART) (Match)
Comments Strong compliance. Good compliance, clarify trim. Strong compliance.
Alternative N/A N/A 4" Valtek MaxFlo4 Rotary, cheaper, similar performance parameters for Cv/Noise. (3822 vs 3821 pos. minor discrepancy)

2. Valve Tag: 131-PV-0586 (Spillback CV)

Feature Masoneilan Samson Flowserve (CTi Controltech)
Valve Model 88-41355 Globe Globe Valve Valtek Mark One-MS Globe (Anti-Noise)
Size/Pipe 4" / 2" Sch. XS (Deviation) DN 6" (63mm seat) / 2" Sch. XS (Significant Deviation) 4" / Pipe 2" Sch. XS (Deviation)
Connection 300# RF (Match) 300# RF (Match) 300# RF (Match)
Fail Pos. FC (Match) FC (Match) FC (Match)
Body Mat. A216 gr WCC (CS - Match) A216 WCC (CS - Match) WCC (CS - Match)
Trim Type LoDB 2 Stage - Linear (Advanced/Anti-Noise) Equal Percentage (Allowed) MegaStream (Anti-Noise) / Equal Percent (Allowed)
Trim Mat. 17-4PH St. St. / 410 St. St. (Match SS) Metallic (Clarify if SS) 416 SS HT (Match SS)
Rated Cv 72 (Req Cv 16.93) - Good margin N/A (Reduced seat, noise focus) 20.077 (Close to req Cv)
Noise 81 dBA (Match ≤ 85) Max 81 dBA for 6" valve (Match ≤ 85) 91 dBA (Deviation > 85, < 115)
Positioner Identical (HART/Smart) Identified in sizing report Logix 3800 Series / 3821 (HART) (Match)
Comments Offers larger valve to manage noise. Offers significantly larger valve to manage noise; clarify intent of pipe size. Offers anti-noise trim; noise level is highest here, but within intermittent limits.

3. Valve Tag: 131-LV-0369 (Waste Water Sep. LV)

Feature Masoneilan Samson Flowserve (CTi Controltech)
Valve Model 28-28111MS Globe Globe Valve Kammer 3850P2 Globe (Small, Precise)
Size/Pipe 1" / 1" Sch. 160 (Match) DN 1" / 1" Sch. 160 (Match) 0.5" / Pipe 1" Sch. 160 (Deviation - valve size)
Connection 300# RF (Match) 300# RF (Match) Flanged (Kammer Std) (Clarify if 300# RF)
Fail Pos. FC (Match) FC (Match) FC (Match)
Body Mat. A351 gr CF3M (316L st.st. - Deviation from CS) A216 WCC (CS - Match) CF3M (316L SS - Deviation from CS)
Trim Type Multi-stage plug (Good for high DP) Equal Percentage (Allowed) Equal Percent (Allowed)
Trim Mat. Stellite 12 / Stellite (Good for high DP) Metallic (Clarify if SS) 1.4122 (SS - Match SS)
Rated Cv 0.05 / Adj. Cv 0.05 (Req Cv 0.01864) N/A (Small Cv) 0.020 (Matches Flowserve’s sizing calculation)
Noise < 70 dBA (Match ≤ 85) < 70 dBA (Match ≤ 85) < 70 dBA (Match ≤ 85)
Positioner Identical (HART/Smart) Identified in sizing report Logix 3800 Series / 3821 (HART) (Match)
Comments Offers SS body and multi-stage trim (suitable for high DP, potential cavitation). Matches CS body. Clarify trim material. Quotes a smaller valve size (0.5"), possibly for better control of very low flows. Has SS body.

4. Valve Tag: 131-FV-0065 (Regeneration Gas To Flare)

Feature Masoneilan Samson Flowserve (CTi Controltech)
Valve Model 88-41325 Globe Globe Valve Valtek Mark One Globe
Size/Pipe 4" / 4" Sch. XS (Match) DN 3" / 4" Sch. XS (Deviation) 3" / Pipe 4" Sch. XS (Deviation)
Connection 300# RF (Match) 300# RF (Match) 300# RF (Match)
Fail Pos. FC (Deviation - Table 1 is FO) FO (Match) FC (Deviation - Table 1 is FO)
Body Mat. A216 gr WCC (CS - Match) A216 WCC (CS - Match) WCC (CS - Match)
Trim Type Equal Percent Contoured (Match) Equal Percentage (Match) Standard / Linear (Match)
Trim Mat. 17-4PH St. St. / 410 St. St. (Match SS) Metallic (Clarify if SS) 316 SS (Match SS)
Rated Cv 225 (Req Cv 72.56) - Good margin N/A 74.697 (matches Flowserve’s sizing calculation)
Noise < 70 dBA (Match ≤ 85) < 70 dBA (Match ≤ 85) 70 dBA (Match ≤ 85)
Positioner Identical (HART/Smart) Identified in sizing report Logix 3800 Series / 3821 (HART) (Match)
Comments Fail position mismatch. Good sized valve. Correct fail position. Size reduction to 3". Fail position mismatch. Offers a 3" valve, and a cheaper 3" rotary alternative.
Alternative N/A N/A 3" Valtek MaxFlo4 Rotary, cheaper. (3822 vs 3821 pos. minor discrepancy)

5. Valve Tag: 131-PV-0597 (Reboiler Gas PV)

Feature Masoneilan Samson Flowserve (CTi Controltech)
Valve Model 88-21114EB Globe Globe Valve Valtek Mark One Globe
Size/Pipe 1" / 1" Sch. XS (Match) 1" / 1" Sch. 160 (Deviation from XS) 1" / Pipe 1" Sch. XS (Match)
Connection 300# RF (Match) 300# RF (Match) 300# RF (Match)
Fail Pos. FC (Match) FC (Match) FC (Match)
Body Mat. A352 gr LCC (LTCS - Match) A352 LCC (LTCS - Match) LCC (LTCS - Match)
Trim Type Linear, Close Clearance (Allowed) Equal Percentage (Allowed) Equal Percent (Allowed)
Trim Mat. Integral w/ seat ring / Stellite (Match SS) Metallic (Clarify if SS) 316 SS (Match SS)
Rated Cv 0.3 (Req Cv 0.1513) N/A 0.152 (matches Flowserve’s sizing calculation)
Noise < 70 dBA (Match ≤ 85) < 70 dBA (Match ≤ 85) < 70 dBA (Match ≤ 85)
Positioner Identical (HART/Smart) Identified in sizing report Logix 3800 Series / 3821 (HART) (Match)
Comments Strong compliance. Minor pipe schedule deviation. Strong compliance.

6. Valve Tag: 131-LV-0376 (Recovered HC CV)

Feature Masoneilan Samson Flowserve (CTi Controltech)
Valve Model 88-21124EB Globe Globe Valve Valtek Mark One Globe
Size/Pipe 2" / 2" Sch. XS (Match) DN 1" / 2" Sch. XS (Deviation) 1" / Pipe 2" Sch. XS (Deviation)
Connection 300# RF (Match) 300# RF (Match) 300# RF (Match)
Fail Pos. FC (Match) FC (Match) FC (Match)
Body Mat. A352 gr LCC (LTCS - Match) A352 LCC (LTCS - Match) LCC (LTCS - Match)
Trim Type Equal Percent Contoured (Match) Equal Percentage (Match) Equal Percent (Match)
Trim Mat. 316 St. St. / 316 St. St. (Match SS) Metallic (Clarify if SS) 316 SS (Match SS)
Rated Cv 15 (Req Cv 5.148) - Good margin N/A 5.211 (matches Flowserve’s sizing calculation)
Noise < 70 dBA (Match ≤ 85) < 70 dBA (Match ≤ 85) < 70 dBA (Match ≤ 85)
Positioner Identical (HART/Smart) Identified in sizing report Logix 3800 Series / 3821 (HART) (Match)
Comments Strong compliance. Size reduction to 1". Size reduction to 1".

7. Valve Tag: 131-TV-0385 (Reboiler Temp CV)

Feature Masoneilan Samson Flowserve (CTi Controltech)
Valve Model 88-21124 Globe Globe Valve Valtek Mark One Globe
Size/Pipe 3" / 3" Sch. XS (Match) DN 1 1/2" / 3" Sch. XS (Deviation) 1.5" / Pipe 3" Sch. XS (Deviation)
Connection 300# RF (Match) 300# RF (Match) 300# RF (Match)
Fail Pos. FC (Match) FC (Match) FC (Match)
Body Mat. A216 gr WCC (CS - Match) A216 WCC (CS - Match) WCC (CS - Match)
Trim Type Equal Percent Contoured (Match) Equal Percentage (Match) Equal Percent (Match)
Trim Mat. 316 St. St. Hard Faced Seat (Match SS) Metallic (Clarify if SS) 316 SS (Match SS)
Rated Cv 6 (Req Cv 2.624) - Good margin N/A 2.698 (matches Flowserve’s sizing calculation)
Noise 71 dBA (Match ≤ 85) N/A 74 dBA (Match ≤ 85)
Positioner Identical (HART/Smart) Identified in sizing report Logix 3800 Series / 3821 (HART) (Match)
Comments Strong compliance. Size reduction to 1.5", clarify trim. Size reduction to 1.5".

8. Valve Tag: 131-PV-0591 (Membrane PCV)

Feature Masoneilan Samson Flowserve (CTi Controltech)
Valve Model 88-21914EB Globe Globe Valve Valtek Mark One-MS Globe (Anti-Noise)
Size/Pipe 3" / 4" Sch. XS (Deviation) DN 3" / 4" Sch. XS (Deviation) 2" / Pipe 4" Sch. XS (Deviation)
Connection 300# RF (Match) 300# RF (Match) 300# RF (Match)
Fail Pos. FC (Match) FC (Match) FC (Match)
Body Mat. A352 gr LCC (LTCS - Match) A352 LCC (LTCS - Match) LCC (LTCS - Match)
Trim Type LoDB 2 Stage - Linear, Multi-Hole (Anti-Noise) Equal Percentage (Match) MegaStream (Anti-Noise) / Equal Percent (Match)
Trim Mat. 316 St. St. Hard Faced Seat / CA6NM St. St. (Match SS) Metallic (Clarify if SS) 416 SS HT (Match SS)
Rated Cv 40 (Req Cv 8.374) - Good margin N/A 9.822 (Matches Flowserve’s sizing calculation)
Noise 74 dBA (Match ≤ 85) N/A 78 dBA (Match ≤ 85)
Positioner Identical (HART/Smart) Identified in sizing report Logix 3800 Series / 3821 (HART) (Match)
Comments Size reduced to 3". Size reduced to 3". Valve size reduced to 2".

9. Valve Tag: 131-TV-0371 (Ref Propane Valve)

Feature Masoneilan Samson Flowserve (CTi Controltech)
Valve Model 88-21714EB Globe Globe Valve Valtek Mark One Globe
Size/Pipe 1.5" / 2" Sch. XS (Deviation - valve size) 2" / 2" Sch. XS (Match) 1.5" / Pipe 2" Sch.XS (Deviation - valve size)
Connection 300# RF (Match) 300# RF (Match) 300# RF (Match)
Fail Pos. FC (Match) FC (Match) FC (Match)
Body Mat. A352 gr LCC (LTCS - Match) A352 LCC (LTCS - Match) LCC (LTCS - Match)
Trim Type Anti-Cavitation 1 Stage (Good for cavitating) Equal Percentage (Match) Equal Percent (Match)
Trim Mat. 316 St. St. Hard Faced Seat (Match SS) Metallic (Clarify if SS) 316 SS / Alloy 6 (Match SS)
Rated Cv 8 (Req Cv 0.9732) - Good margin N/A 7.352 (matches Flowserve’s sizing calculation)
Noise < 70 dBA (Match ≤ 85) < 70 dBA (Match ≤ 85) Flashing* (Note: Flashing implies noise is inevitable)
Positioner Identical (HART/Smart) Identified in sizing report Logix 3800 Series / 3821 (HART) (Match)
Comments Offers anti-cavitation trim. Good size match. Clarify trim. Offers a 1.5" valve. Has a cheaper 1" rotary alternative.
Alternative N/A N/A 1" Valtek MaxFlo4 Rotary, cheaper. (3822 vs 3821 pos. minor discrepancy)

10. Valve Tag: 131-LV-0372 (Memb Sep LV)

Feature Masoneilan Samson Flowserve (CTi Controltech)
Valve Model 88-21124EB Globe Globe Valve Valtek Mark One Globe
Size/Pipe 2" / 2" Sch. XS (Match) DN 1" / 2" Sch. XS (Deviation) 1" / Pipe 2" Sch. XS (Deviation)
Connection 300# RF (Match) 300# RF (Match) 300# RF (Match)
Fail Pos. FC (Match) FC (Match) FC (Match)
Body Mat. A352 gr LCC (LTCS - Deviation from CS) A352 LCC (LTCS - Deviation from CS) LCC (LTCS - Deviation from CS)
Trim Type Equal Percent Contoured (Match) Equal Percentage (Match) Equal Percent (Match)
Trim Mat. 316 St. St. / 316 St. St. (Match SS) Metallic (Clarify if SS) 316 SS / Alloy 6 (Match SS)
Rated Cv 3.8 (Req Cv 1.471) - Good margin N/A 2.591 (matches Flowserve’s sizing calculation)
Noise < 70 dBA (Match ≤ 85) < 70 dBA (Match ≤ 85) Flashing* (Note: Flashing implies noise is inevitable)
Positioner Identical (HART/Smart) Identified in sizing report Logix 3800 Series / 3821 (HART) (Match)
Comments All vendors deviate on body material (quote LTCS instead of CS). Masoneilan best on pipe size. Size reduced to 1". Offers a 1" valve. Has a cheaper 1" rotary alternative.
Alternative N/A N/A 1" Valtek MaxFlo4 Rotary, cheaper. (3822 vs 3821 pos. minor discrepancy)

11. Valve Tag: 131-TV-0361 (Glycol Water CV)

Feature Masoneilan Samson Flowserve (CTi Controltech)
Valve Model 88-21114 Globe Globe Valve Valtek Mark One Globe
Size/Pipe 3" / 6" Sch. XS (Deviation) DN 3" / 6" Sch. XS (Deviation) 3" / Pipe 6" Sch. XS (Deviation)
Connection 300# RF (Match) 300# RF (Match) 300# RF (Match)
Fail Pos. FC (Match) FC (Match) FC (Match)
Body Mat. A352 gr LCC (LTCS - Deviation from CS) A216 WCC (CS - Match) WCC (CS - Match)
Trim Type Linear Contoured (Match) Equal Percentage (Match) Standard / Linear (Match)
Trim Mat. 410 St. St. / 410 St. St. (Match SS) Metallic (Clarify if SS) 316 SS (Match SS)
Rated Cv 110 (Req Cv 61.14) - Good margin N/A 59.664 (matches Flowserve’s sizing calculation)
Noise < 70 dBA (Match ≤ 85) < 70 dBA (Match ≤ 85) < 70 dBA (Match ≤ 85)
Positioner Identical (HART/Smart) Identified in sizing report Logix 3800 Series / 3821 (HART) (Match)
Comments All vendors quote a 3" valve for a 6" line. Masoneilan quotes LTCS body. Good body material match. Clarify trim. Offers a 3" valve. Has a cheaper 3" rotary alternative.
Alternative N/A N/A 3" Valtek MaxFlo4 Rotary, cheaper. (3822 vs 3821 pos. minor discrepancy)

Missing Valves (from Table 1)

All three vendors (Masoneilan, Samson, Flowserve) did not include quotes for the following valves from your “Table 1”:

This is a critical gap in all quotes and must be addressed as a priority with all vendors.


Cost Summary (for the 11 quoted valves)


Actionable Recommendations for Picking a Vendor

  1. Address Missing Valves IMMEDIATELY: Contact all three vendors and request quotes for 131-PCV-0583, 131-PCV-0585C, and 131-PV-0581. This is non-negotiable for a complete project.

  2. Review Valve Size Deviations:

  3. Clarify Specific Material & Fail Position Mismatches:

  4. Evaluate Noise Performance:

  5. Consider Flowserve’s Rotary Alternatives:

  6. Lead Time: All quoted lead times seem similar. Ensure the lead time for the missing valves doesn’t significantly impact project schedule.


Preliminary Conclusion (Pending Clarifications & Missing Valves):

Based on the provided data for the 11 valves quoted:

Next Steps:

  1. Send a formal RFI (Request for Information) to all three vendors, specifically asking for:
  2. Once you receive their responses, update this comparison table and re-evaluate. The decision will likely come down to technical compliance, justified deviations, and final pricing.